Alarms

Alarms

Level

The level alarm is the most common. Use this alarm to warn you when your process is in danger of being upset due to high or low levels.

Generally, the four alarms used are Hi, Hi Hi, Lo, and Lo Lo.

Set the Common Parameters

P006

hi hi

hi

P007

lo

lo lo

Prerequisite: You must know the details of your application and substitute the values for the sample values provided. If you are bench testing the unit, then set your test values to be the same as the sample values.

Parameter

P001

P002

P003

P004

P005

P006

P007

Index1

G

G

G

G

G

G

G

Value

1

1

2

102

1

1.8

1.4

Description

Operation = level Material = liquid

Maximum Process Speed = medium Transducer = XPS-10

Units = meters Empty = 1.8m Span = 1.4m

1.This example assumes a base, single measurement unit. If your unit has optional dual point software installed then some parameters are indexed by two.

Page 54

MultiRanger 100/200 – INSTRUCTION MANUAL

7ML19981FB06

Page 64