P136 Wall Cling Reduction [MR 200]

Varies the upper and lower setpoints to reduce material buildup on the walls.

Primary Index

Single Point Model

Dual Point Model

 

 

Global

Transducer

 

 

 

 

Values

Range: 0.000 to 9999

 

 

 

Preset: 0.000

 

 

 

 

 

 

This value is the range in which the setpoints are allowed to deviate in percent or units. The Relay Setpoints ON and OFF values are randomly varied inside the range to ensure that the material level does not consistently stop at the same point.

Random Setpoint Range

Level Setpoint ON

Wall Cling Value

Level Setpoint OFF

P137 Pump Group [MR 200]

Puts pumps into groups for multiple pump rotations on one transducer.

Primary Index

Relay

 

 

 

 

Range: 1 to 2

Values

 

 

 

1

*

group 1

 

 

 

 

 

2

 

group 2

 

 

 

 

Alters

P111 Relay Control Function when P111=52 (Alternate duty

 

assist) or 53 (Alternate duty backup)

 

 

 

 

 

 

This feature groups pumps (relay points 1 - 6) into groups 1 or 2. It is applied to pump rotation and occurs independently within each group.

7ML19981FB06

MultiRanger 100/200 – INSTRUCTION MANUAL

Page 143

Parameters