P701 Max Empty Rate

Adjusts the MultiRanger response to decreases in the actual material level (or advance to a lower Failsafe Material Level, P071).

Primary Index

 

Single Point Model

Dual Point Model

 

 

 

Global

Transducer

 

 

 

 

Values

Range: 0.000 to 99.00 m (or equivalent depending on units)

 

 

Altered by

• P003 Maximum Process Speed

 

 

 

 

 

P005 Units

 

Related

P007 Span

 

 

• P071 Failsafe Material Level

 

 

 

 

 

Enter a value slightly greater than the maximum vessel emptying rate. This value, in Units (P005) or % of Span (P007) per minute, is automatically altered when Maximum Process Speed (P003) is altered.

P003 Value

Meters / Minute

1

0.1

 

 

2

1

3

10

 

 

P702 Filling Indicator

The fill rate required to activate the LCD Filling indicator ().

Primary Index

 

Single Point Model

Dual Point Model

 

 

 

 

Global

 

Transducer

 

 

 

 

 

Values

Range: 0.000 to 99.00 m (or equivalent depending on units)

 

 

 

Altered by

P003 Maximum Process Speed

 

 

 

 

 

 

P005

Units

 

Related

P007 Span

 

 

• P700

Max Fill Rate

 

 

 

 

 

 

This value (in Units (P005) or % of Span (P007) per minute) is automatically set to 1/10 of the Max Fill Rate (P700).