Parameters

mA Output (P200 to P219)

P200 mA Output Range

Determines the mA output range.

Primary Index

mA output

 

 

 

 

 

0

 

off

 

 

 

 

 

1

 

0 to 20 mA

Values

 

 

 

2

*

4 to 20 mA

 

 

 

 

 

3

 

20 to 0 mA

 

 

 

 

 

4

 

20 to 4 mA

 

 

 

 

Related

P911 mA Output Value

 

 

 

 

If either 1 or 2 is selected, the mA output is directly proportional to the mA Function. If either 3 or 4 is selected, then the output is inversely proportional. After setting P200, verify that P212 has a valid entry for mA Output Min Limit, as P212 is not changed automatically by a change to P200.

P201 mA Output Function

Alters the mA output/measurement relationship.

Please note that parameter P201 values vary between the MultiRanger 100 and the MultiRanger 200.

MultiRanger 100

Primary Index

mA output

 

 

 

 

 

 

 

 

 

value

 

mA function

 

Operation (P001)

 

 

 

 

 

 

 

 

0

 

 

OFF

 

 

Values

 

 

 

 

 

 

1

 

 

level

 

level

 

 

 

 

 

 

 

 

2

 

 

space

 

space

 

 

 

 

 

 

 

 

3

 

 

distance

 

distance

 

 

 

 

 

Related

P202 mA Output Allocation

P911 mA Output Value

 

 

 

 

 

 

 

Altered By

P001 Operation

 

 

 

 

 

 

 

 

Page 146

MultiRanger 100/200 – INSTRUCTION MANUAL

7ML19981FB06

Page 156
Image 156
Siemens MA Output P200 to P219, P200 mA Output Range, P201 mA Output Function, Determines the mA output range