Operation

Status Parameters

Status parameters give the operating status of the MultiRanger. You can access parameters with the hand programmer (see page 32) or with Dolphin Plus (see page 27). Remote SCADA system access is also possible.

Parameter

P203

P254

[MR 200 only]

P275

P322

[MR 200 only]

P323

[MR 200 only]

P341

P342

P664

P707

P708

[MR 200 only]

P729

P806

P920

P921

P922

P924

[MR 200 only]

P925

[MR 200 only]

P926

[MR 200 only]

P927

mA Output Value Scaled mA Input Value

Scaled Discrete Input Value

LCD Total Low

LCD Total High

Run Time

Start Ups

Temperature

Rate Value

Volume Rate Display

Scan Time

Echo Strength

Reading Measurement

Material Measurement

Space Measurement

Volume Measurement

Flow Measurement (OCM)

Head Measurement (OCM)

Distance Measurement

Values

0 to 22 – Current mA output

0 to 9999 – Current mA input after scaling

Shows current value of discrete input, values vary by DI function

The last four digits of the totalizer

The first four digits of the totalizer

The number of days the MultiRanger has been operating

The number of times power has been cycled

Current temperature measured by transducer

Current rate of material level change Current rate of material volume change

Seconds since last level scan Strength of primary echo Current primary reading Current level from P007–Span Empty space above the material level Current volume value, if programmed

Current flow value, if OCM programmed

Current level, if OCM programmed

Distance from transducer face to material

Page 24

MultiRanger 100/200 – INSTRUCTION MANUAL

7ML19981FB06