Siemens 200 instruction manual Preset Applications, Value Parameters Affected

Models: 200

1 282
Download 282 pages 42.81 Kb
Page 56
Image 56

Relays

Preset Applications

Preset applications set up the relay parameters to predetermined values shown below:

Value

#

Parameters Affected

Off

0

All relays set to OFF

Wet Well 1

 

Pump down with the following settings:

 

Parameter

 

 

Relay #

 

 

 

1

2

3

4

5

6

 

 

1

P111

52

52

1(H)

1(L)

0

0

 

P112

70%

80%

90%

10%

 

P113

20%

20%

85%

15%

Wet Well 2

Pump down with the following level and rate settings:

 

 

 

Parameter

 

 

Relay #

 

 

 

1

2

3

4

5

6

 

 

 

P111

52

52

1(H)

1(L)

0

0

 

P112

70%

80%

90%

10%

2

P113

20%

20%

85%

15%

 

P121

 

 

1

 

 

 

 

P121 sets the pump relays to accept control by rate of level change once

 

the first ON setpoint is reached. Because the pumps are started by rate,

 

you must change P703 to desired empty rate.

 

 

 

Reservoir 1

Pump up with the following level settings:

 

 

 

 

Parameter

 

 

Relay #

 

 

 

1

2

3

4

5

6

 

 

3

P111

52

52

1(H)

1(L)

0

0

 

P112

30%

20%

90%

10%

 

P113

80%

80%

85%

15%

Reservoir 2

Pump up with the following level and rate settings:

 

 

 

Parameter

 

 

Relay #

 

 

 

1

2

3

4

5

6

 

 

 

P111

52

52

1(H)

1(L)

0

0

 

P112

20%

20%

90%

10%

4

P113

80%

80%

85%

15%

 

P121

 

 

1

 

 

 

 

P121 sets the pump relays to accept control by rate of level change once

 

the first ON setpoint is reached. Because the pumps are started by rate

 

you must change P702 to desired fill rate.

 

 

 

Screen

Differential control of a screen or rake:

 

 

 

 

Parameter

 

 

Relay #

 

 

 

1

2

3

4

5

6

 

 

5

P110

3

1

2

3

0

0

 

P111

50

1(H)

1(L)

1(H)

 

P112

80%

90%

10%

90%

 

P113

20%

85%

15%

10%

Alarms

General alarms at four setpoints:

 

 

 

 

 

Parameter

 

 

Relay #

 

 

 

1

2

3

4

5

6

 

 

6

P111

1(H)

1(L)

1(HH)

1(LL)

0

0

 

P112

80%

20%

90%

10%

 

P113

75%

25%

85%

15%

Page 46

MultiRanger 100/200 – INSTRUCTION MANUAL

7ML19981FB06

Page 56
Image 56
Siemens 200 instruction manual Preset Applications, Value Parameters Affected