Transducers

Warning: Hazardous voltage present on transducer terminals during operation.

Run the transducer cable in a grounded metal conduit, separate from other wiring (except TS-3 temperature sensor wiring, if applicable).

Notes:

Do not use coaxial cable because of electrical noise interference

Do not connect the shield and white transducer wires together; wire to separate terminals

Disregard older transducer manuals that recommend these practices

white

TRANSDUCER TWO

black

white

TRANSDUCER ONE

black

A 0.1 µF (100V or greater) capacitor is included with the MultiRanger for retrofitting old MultiRanger Plus installations. Please see MultiRanger 100/200 Installation (for retrofitting MultiRanger Plus Installations) on page 247.

Relays

Relay contacts are shown in the de-energized position. All relays are handled identically and can be configured as positive or negative logic using P118.

Relay Ratings

four Form A, NO relays(1,2,4,5)

two Form C, NO or NC relays (3,6)

5A at 250Vac, non- inductive

RELAY 1

RELAY 2

RELAY 3

RELAY 4

RELAY 5

RELAY 6

Power Failure

Relays 1, 2, 4, and 5 are normally open and will fail in the normal state.

Relays 3 and 6 can be wired either normally open or normally closed, and will fail in their de- energized states.

Wiring

7ML19981FB06

MultiRanger 100/200 – INSTRUCTION MANUAL

Page 17

Page 27
Image 27
Siemens 200 instruction manual Transducers, Relays, Relay Ratings, Power Failure, 5A at 250Vac, non- inductive