Siemens 200 Independent mA Setpoints P210 and P211, MA Output Limits P212 and P213

Models: 200

1 282
Download 282 pages 42.81 Kb
Page 159
Image 159

Independent mA Setpoints (P210 and P211)

Use these features to reference the minimum and/or maximum mA output to any point in the measurement range.

P201—mA Function

Action

Settings

 

 

 

Level, Space, or Distance

Enter the material level in Units (P005) or percent of

Span (P007) as referenced to Empty (P006).

 

 

 

Volume [MR 200]

Enter the volume in Max Volume (P051) units or as a per-

cent of Max Volume.

 

 

 

Flow [MR 200]

Enter the flowrate in OCM Max Flow (P604) units or as a

percent of OCM Max Flow.

 

 

 

Head [MR 200]

Enter the head in level units (P005) or percent of Max

Head (P603).

 

 

 

Volume Rate [MR 200]

Enter the volume rate in volume/min. Ensure the % sym-

bol is displayed before attempting to enter a % value.

 

 

 

mA input or

Not Applicable

Communications Input

 

 

 

P210 0/4 mA Output Setpoint

Sets the process level corresponding to the 0 or 4mA value.

Primary Index

mA output

 

 

Values

Range: -999 to 9999

 

 

 

Related

P211 20 mA Output Setpoint

 

 

 

Enter the value (in applicable units or %) to correspond to 0 or 4 mA.

P211 20 mA Output Setpoint

Sets the process level that corresponds to the 20 mA value.

Primary Index

mA output

 

 

Values

Range: -999 to 9999

 

 

 

Related

P210 0/4 mA Output Setpoint

 

 

 

Enter the value (in applicable units or %) to correspond to 20 mA.

mA Output Limits (P212 and P213)

Use these features to adjust the minimum and/or maximum mA output values, which should suit the input limit requirements of the external device.

7ML19981FB06

MultiRanger 100/200 – INSTRUCTION MANUAL

Page 149

Parameters

Page 159
Image 159
Siemens 200 Independent mA Setpoints P210 and P211, MA Output Limits P212 and P213, P210 0/4 mA Output Setpoint