Page 58 MultiRanger 100/200 – INSTRUCTION MANUAL 7ML19981FB06
mmmmm
Pump Control
Pump Con trol

Setting a Pump Down Grou p

Example: Sewage Wet Well
Setting a group of three pumps to pump down a wet well.
Set the Common Parameters
Prerequisite: Substitute the details of your application in place of the sample values
provided. If you are bench testing the unit, set your test values to be the same as the
sample values.
Paramete r Index1
1. Example assumes a single measurement unit. If your MultiRanger has
dual point software installed then some parameters are indexed by two.
Value Descripti on
P001 G 1 Operation = level
P002 G 1 Material = liquid
P003 G 2 Maximum Process Speed = medium
P004 G102 Transducer = XPS-10
P005 G 1 Units = meters
P006 G1.8 Empty = 1.8m
P007 G 1.4 Span = 1.4m
MultiRanger
P006
P007
Inflow
Outflow