Pump Control

Setting a Pump Down Group

Example: Sewage Wet Well

Setting a group of three pumps to pump down a wet well.

Pump Control

Inflow

MultiRanger

P006

Outflow

P007

Set the Common Parameters

Prerequisite: Substitute the details of your application in place of the sample values provided. If you are bench testing the unit, set your test values to be the same as the sample values.

Parameter

P001

P002

P003

P004

P005

P006

P007

Index1

G

G

G

G

G

G

G

Value

1

1

2

102

1

1.8

1.4

Description

Operation = level Material = liquid

Maximum Process Speed = medium Transducer = XPS-10

Units = meters Empty = 1.8m Span = 1.4m

1.Example assumes a single measurement unit. If your MultiRanger has dual point software installed then some parameters are indexed by two.

Page 58

MultiRanger 100/200 – INSTRUCTION MANUAL

7ML19981FB06

Page 68
Image 68
Siemens 200 instruction manual Pump Control, Setting a Pump Down Group, Example Sewage Wet Well