Chapter 4 Parameters

10 to +10V from AVI

24 to 20mA from ACI or 0 to +10V from AVI2

3RS-485 (RJ-45)/USB communication

4Digital keypad potentiometer

5CANopen communication

These parameters set the Master Frequency Command Source of the AC motor drive.

The factory setting for master frequency command is 1. (digital keypad is optional.)

Setting 2: use the ACI/AVI switch on the AC motor drive to select ACI or AVI2. When setting to

AVI, AVI2 is indicated.

When the 3rd switch on the upper-right corner is set to be ON as shown in the following

diagram, the source of first master frequency command (Pr.02.00) will force setting to 2. This

setting(Pr.02.00) can’t be changed till the 3rd switch is set to be OFF.

ON

1 2

3

When the AC motor drive is controlled by external terminal, please refer to Pr.02.05 for details.

The first /second frequency/operation command is enabled/disabled by Multi Function Input

Terminals. Please refer to Pr.04.05 ~ 04.08.

02.01Source of First Operation Command

 

 

Factory Setting: 1

Settings

0

Digital keypad (Digital keypad is optional)

 

1

External terminals. Keypad STOP/RESET enabled.

 

2

External terminals. Keypad STOP/RESET disabled.

 

3

RS-485 (RJ-45)/USB communication. Keypad STOP/RESET

 

 

enabled.

 

4

RS-485 (RJ-45)/USB communication. Keypad STOP/RESET

 

 

disabled.

 

5

CANopen communication. Keypad STOP/RESET disabled.

 

 

 

The factory setting for source of first operation command is 1. (digital keypad is optional.)

When the AC motor drive is controlled by external terminal, please refer to Pr.02.05/Pr.04.04

for details.

02.10Combination of the First and Second Master Frequency Command

Factory Setting: 0

Revision June 2008, 04EE, SW--PW V1.11/CTL V2.11

4-51