Chapter 4 Parameters

 

Group 2 Operation Method Parameters

 

 

 

 

 

 

 

Parameter

Explanation

Settings

Factory

Customer

Setting

 

 

0: Digital keypad UP/DOWN keys or Multi-

 

 

 

 

function Inputs UP/DOWN. Last used

 

 

 

 

frequency saved.

 

 

02.00

Source of First

1: 0 to +10V from AVI

1

 

Master Frequency

2: 4 to 20mA from ACI or 0 to +10V from

 

 

Command

 

 

 

AVI2

 

 

 

 

 

 

 

 

3: RS-485 (RJ-45)/USB communication

 

 

 

 

4: Digital keypad potentiometer

 

 

 

 

5: CANopen communication

 

 

 

 

 

 

 

 

 

0: Digital keypad

 

 

 

 

1: External terminals. Keypad STOP/RESET

 

 

 

 

enabled.

 

 

 

 

2: External terminals. Keypad STOP/RESET

 

 

 

Source of First

disabled.

 

 

02.01

Operation

3: RS-485 (RJ-45)/USB communication.

1

 

 

Command

 

 

 

Keypad STOP/RESET enabled.

 

 

 

 

 

 

 

 

4: RS-485 (RJ-45)/USB communication.

 

 

 

 

Keypad STOP/RESET disabled.

 

 

 

 

5: CANopen communication. Keypad

 

 

 

 

STOP/RESET disabled.

 

 

 

 

 

 

 

 

 

0: STOP: ramp to stop; E.F.: coast to stop

 

 

02.02

Stop Method

1: STOP: coast to stop; E.F.: coast to stop

0

 

2: STOP: ramp to stop; E.F.: ramp to stop

 

 

 

 

 

 

 

3: STOP: coast to stop; E.F.: ramp to stop

 

 

 

 

 

 

 

 

PWM Carrier

 

 

 

02.03

Frequency

1 to 15kHz

8

 

 

Selections

 

 

 

 

 

 

 

 

 

 

0: Enable forward/reverse operation

 

 

02.04

Motor Direction

1: Disable reverse operation

0

 

Control

 

 

 

 

 

 

 

2: Disabled forward operation

 

 

 

 

 

 

 

02.05

Line Start Lockout

0: Disable. Operation status is not changed

1

 

even if operation command source Pr.02.01

 

 

 

is changed.

 

 

 

 

1: Enable. Operation status is not changed

 

 

 

 

even if operation command source Pr.02.01

 

 

 

 

is changed.

 

 

 

 

 

 

 

Revision June 2008, 04EE, SW--PW V1.11/CTL V2.11