Chapter 4 Parameters

04.04External Terminal

 

 

STOP RUN

MI1:("CLOSE":RUN)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

3-wire

 

 

 

 

 

 

 

 

 

 

 

MI3:("OPEN":STOP)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MI2:("OPEN": FWD)

 

 

 

 

 

 

 

 

REV/FWD

("CLOSE": REV)

DCM

VFD-E

04.05Multi-function Input Terminal (MI3)

Factory Setting: 1

04.06Multi-function Input Terminal (MI4)

Factory Setting: 2

04.07Multi-function Input Terminal (MI5)

Factory Setting: 3

04.08Multi-function Input Terminal (MI6)

Factory Setting: 4

Settings

Function

Description

 

 

 

0

No Function

Any unused terminals should be programmed to 0 to insure they

have no effect on operation.

 

 

 

 

 

1

Multi-Step Speed

These four inputs select the multi-speed defined by Pr.05.00 to

Command 1

 

 

Pr.05.14 as shown in the diagram at the end of this table.

 

 

2

Multi-Step Speed

 

Command 2

 

 

NOTE: Pr.05.00 to Pr.05.14 can also be used to control output

 

 

 

Multi-Step Speed

3

speed by programming the AC motor drive’s internal PLC

Command 3

function. There are 17 step speed frequencies (including

 

 

 

Master Frequency and Jog Frequency) to select for

 

Multi-Step Speed

4

application.

Command 4

 

 

 

 

 

 

 

The External Reset has the same function as the Reset key on

5

External Reset

the Digital keypad. After faults such as O.H., O.C. and O.V. are

 

 

cleared this input can be used to reset the drive.

 

 

 