Chapter 4 Parameters

 

 

 

 

12.05

Max. AVI3 Scale Percentage

 

Unit: 0.1

 

 

 

 

 

 

 

Settings

0.0 to 100.0%

 

Factory Setting: 100.0

 

 

 

 

 

 

 

 

12.06

Min. ACI2 Input Current

 

Unit: 0.1

 

 

 

 

 

 

 

Settings

0.0 to 20.0mA

 

Factory Setting: 4.0

 

 

 

 

 

 

 

 

12.07

Min. ACI2 Scale Percentage

 

Unit: 0.1

 

 

 

 

 

 

 

Settings

0.0 to 100.0%

 

Factory Setting: 0.0

 

 

 

 

 

 

 

 

12.08

Max. ACI2 Input Current

 

Unit: 0.1

 

 

 

 

 

 

 

Settings

0.0 to 20.0mA

 

Factory Setting: 20.0

 

 

 

 

12.09

Max. ACI2 Scale Percentage

 

Unit: 0.1

 

 

 

 

 

 

 

Settings

0.0 to 100.0%

 

Factory Setting: 100.0

 

 

 

 

 

 

 

 

12.10

AI2 Function Selection

 

 

 

 

 

 

 

 

 

 

 

 

 

Factory Setting: 0

 

Settings

0

Disabled

 

 

1Source of the 1st frequency

2Source of the 2nd frequency

3PID Set Point (PID enable)

4Positive PID feedback

5Negative PID feedback

12.11AI2 Analog Signal Mode

Factory Setting: 1

Settings

0

ACI3 analog current (0.0 ~ 20.0mA)

 

1

AVI4 analog voltage (0.0 ~ 10.0V)

 

 

 

Besides parameters settings, the voltage/current mode should be used with the switch.