Chapter 4 Parameters

04.17

Maximum ACI Current

Unit: 0.01

 

Settings

0.0 to 20.0mA

Factory Setting: 20.0

 

 

 

04.18

Maximum ACI Frequency (percentage of Pr. 01.00)

Unit: 0.1

 

 

 

 

 

Settings

0.0 to 100.0%

Factory Setting: 100.0

04.19ACI Terminal Mode Selection

 

 

 

 

 

Factory Setting: 0

 

Settings

0

ACI

 

 

 

 

1

AVI2

 

 

 

 

 

 

04.20

Minimum AVI2 Voltage

 

Unit: 0.1

 

Settings

0.0 to 10.0V

 

Factory Setting: 0.0

 

 

 

 

04.21

Minimum AVI2 Frequency

(percentage of Pr.1-00)

Unit: 0.1

 

Settings

0.0 to 100.0%

Factory Setting: 0.0

 

 

 

 

04.22

Maximum AVI2 Voltage

 

Unit: 0.1

 

Settings

0.0 to 10.0V

 

Factory Setting: 10.0

 

 

 

 

04.23

Maximum AVI2 Frequency

(percentage of Pr.1-00)

Unit: 0.1

 

Settings

0.0 to 100.0%

Factory Setting: 100.0

 

 

 

 

 

 

Please note the ACI/AVI switch on the AC motor drive. Switch to ACI for 4 to 20mA analog current signal (ACI) (Pr.04.19 should be set to 0) and AVI for analog voltage signal (AVI2) (Pr.04.19 should be set to 1).

The above parameters are used to set the analog input reference values. The min and max frequencies are based on Pr.01.00 (during open-loop control) as shown in the following.

01.00

04.14

04.18

04.12

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

04.16

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

04.11

 

 

04.21

 

 

 

04.17

 

 

 

04.15

 

 

 

 

 

 

 

04.20

 

04.22

analog input

Revision June 2008, 04EE, SW--PW V1.11/CTL V2.11

4-73

Page 126
Image 126
Delta Electronics VFD-E manual 04.17, 04.18, 04.20, 04.21, 04.22, 04.23