Chapter 4 Parameters

to lower the freqeuency command by PLC or the host controller. On the other hand, it can be high-speed operation.

08.24DEB Function

 

 

 

 

Factory Setting: 0

 

Settings

0

Disable

 

 

 

1

Enable

 

08.25

DEB Return Time

 

Unit: 1

 

 

 

 

 

 

Settings

0~250 sec

Factory Setting: 0

 

 

 

 

 

The DEB (Deceleration Energy Backup) function is the AC motor drive decelerates to stop after momentary power loss. When the momentary power loss occurs, this function can be used for the motor to decelerate to 0 speed with deceleration stop method. When the power is on again, motor will run again after DEB return time. (for high-speed axis application)

Status 1: Insufficient power supply due to momentary power-loss/unstable power (due to low voltage)/sudden heavy-load

 

DC BUS voltage

 

 

 

 

 

The level for DEB return time

 

it doesn't need

 

(Lv=+30V+58V)

 

multi-function terminals

The level for soft start relay to be ON

 

 

 

 

(Lv+30)

Lv level

 

 

 

 

 

 

 

 

 

 

Soft start relay at

 

 

 

 

 

 

 

 

 

 

 

 

power side

 

 

 

 

 

 

DEB function is activated

Output frequency

Pr.07-13 Decel. time selection for momentary power loss

DEB return time

NOTE

07-14

When Pr.07-14 is set to 0, the AC motor drive will be stopped and won't re-start at the power-on again.

Status 2: unexpected power off, such as momentary power loss

4-110

Revision June 2008, 04EE, SW--PW V1.11/CTL V2.11