Delta Electronics VFD-E manual Check if the motor runs steadily

Models: VFD-E

1 363
Download 363 pages 22.75 Kb
Page 53
Image 53

Chapter 3 Keypad and Start Up

3.Setting the potentiometer or AVI-DCM 0-10Vdc power to less than 1V.

4.Setting MI1=On for forward running. And if you want to change to reverse running, you should set MI2=On. And if you want to decelerate to stop, please set MI1/MI2=Off.

5.Check following items:

„Check if the motor direction of rotation is correct.

„Check if the motor runs steadily without abnormal noise and vibration.

„Check if acceleration and deceleration are smooth.

If you want to perform a trial run by using optional digital keypad, please operate by the following steps.

1.

Connect digital keypad to AC motor drive

 

correctly.

 

 

2.

After applying the power, verify that LED

 

display shows F 0.0Hz.

 

3.

Set Pr.02.00=0 and Pr.02.01=0. (Refer to

 

Appendix B operation flow for detail)

4.

Press

key to set frequency to

 

around 5Hz.

 

 

5.

Press

key for forward running.

 

And if you want to change to reverse

 

running, you should press

in

 

 

 

 

page. And if you want to

 

 

 

 

 

decelerate to stop, please press

 

 

key.

 

 

6.

Check following items:

 

„

 

Check if the motor direction of rotation

 

 

is correct.

 

 

„

 

Check if the motor runs steadily

 

 

without abnormal noise and vibration.

„Check if acceleration and deceleration are smooth.

If the results of trial run are normal, please start the formal run.

3-4

Revision June 2008, 04EE, SW--PW V1.11/CTL V2.11

Page 53
Image 53
Delta Electronics VFD-E manual Check if the motor runs steadily