Delta Electronics VFD-E manual Group 7 Motor Parameters Explanation Settings, Fla

Models: VFD-E

1 363
Download 363 pages 22.75 Kb
Page 72
Image 72

 

 

 

Chapter 4 Parameters

 

Group 7 Motor Parameters

 

 

 

 

 

 

 

 

 

 

Parameter

Explanation

Settings

 

Factory

Customer

 

Setting

07.00

Motor Rated Current

30 %FLA to 120% FLA

 

FLA

 

 

(Motor 0)

 

 

 

 

 

 

 

 

 

 

07.01

Motor No-Load

0%FLA to 99% FLA

 

0.4*FLA

 

Current (Motor 0)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Torque

 

 

 

 

07.02

Compensation

0.0 to 10.0

 

0.0

 

 

(Motor 0)

 

 

 

 

 

 

 

 

 

 

07.03

Slip Compensation

0.00 to 10.00

 

0.00

 

 

(Used without PG)

 

 

 

 

 

(Motor 0)

 

 

 

 

 

 

 

 

 

 

 

Motor Parameters

0: Disable

 

 

 

07.04

1: Auto tuning R1

 

0

 

Auto Tuning

 

 

 

2: Auto tuning R1 + no-load test

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Motor Line-to-line

0~65535 mΩ

 

0

 

07.05

Resistance R1

 

 

 

(Motor 0)

 

 

 

 

 

 

 

 

 

 

07.06

Motor Rated Slip

0.00 to 20.00 Hz

 

3.00

 

(Motor 0)

 

 

 

 

 

 

 

 

 

 

 

 

 

07.07

Slip Compensation

0 to 250%

 

200

 

Limit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Torque

 

 

 

 

07.08

Compensation Time

0.01 ~10.00 Sec

 

0.10

 

 

Constant

 

 

 

 

 

 

 

 

 

 

07.09

Slip Compensation

0.05 ~10.00 sec

 

0.20

 

Time Constant

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Accumulative Motor

 

 

 

 

07.10

Operation Time

0 to 1439 Min.

 

0

 

 

(Min.)

 

 

 

 

 

 

 

 

 

 

 

Accumulative Motor

 

 

 

 

07.11

Operation Time

0 to 65535 Day

 

0

 

 

(Day)

 

 

 

 

 

 

 

 

 

 

07.12

Motor PTC

0: Disable

 

0

 

Overheat Protection

1: Enable

 

 

 

 

 

 

 

 

 

 

 

 

 

Input Debouncing

 

 

 

 

07.13

Time of the PTC

0~9999(*2ms)

 

100

 

 

Protection

 

 

 

 

 

 

 

 

 

 

Revision June 2008, 04EE, SW--PW V1.11/CTL V2.11