Delta Electronics VFD-E manual Source Pr.02.01 is changed

Models: VFD-E

1 363
Download 363 pages 22.75 Kb
Page 109
Image 109

Chapter 4 Parameters

02.05Line Start Lockout

 

 

Factory Setting: 1

Settings

0

Disable. Operation status is not changed even if operation

 

 

command source Pr.02.01 is changed.

 

1

Enable. Operation status is not changed even if operation command

 

 

source Pr.02.01 is changed.

 

2

Disable. Operation status will change if operation command source

 

 

Pr.02.01 is changed.

 

3

Enable. Operation status will change if operation command source

 

 

Pr.02.01 is changed.

This parameter determines the response of the drive upon power on and operation command

source is changed.

Pr.02.05

Start lockout (Run when power is ON)

Operation status when operation

command source is changed

 

 

 

 

 

0

Disable (AC motor drive will run)

Keep previous status

 

 

 

1

Enable (AC motor drive doesn’t run)

Keep previous status

 

 

 

2

Disable (AC motor drive will run)

Change according to the new

operation command source

 

 

 

 

 

3

Enable (AC motor drive doesn’t run)

Change according to the new

operation command source

 

 

 

 

 

When the operation command source is from external terminal and operation command is ON (MI1/MI2-DCM=closed), the AC motor drive will operate according to Pr.02.05 after power is applied. <For terminals MI1 and MI2 only>

1.When Pr.02.05 is set to 0 or 2, AC motor drive will run immediately.

2.When Pr.02.05 is set to 1 or 3, AC motor drive will remain stopped until operation command is received after previous operation command is cancelled.

4-56

Revision June 2008, 04EE, SW--PW V1.11/CTL V2.11