Chapter 4 Parameters

Refer to following calculation for protection level and warning level.

1.Protection level

Pr.07.14= V+10 * (RPTC1//47K) / [R1+( RPTC1//47K)]

2.Warning level

Pr.07.16= V+10 * (RPTC2//47K) / [R1+( RPTC2//47K)]

3.Definition:

V+10: voltage between +10V-ACM, Range 10.4~11.2VDC

RPTC1: motor PTC overheat protection level. Corresponding voltage level set in

Pr.07.14, RPTC2: motor PTC overheat warning level. Corresponding voltage level set

in Pr.07.15, 47kΩ: is AVI input impedance, R1: resistor-divider (recommended value: 1~20kΩ)

Take the standard PTC thermistor as example: if protection level is 1330Ω, the voltage between +10V-ACM is 10.5V and resistor-divider R1 is 4.4kΩ. Refer to following calculation for Pr.07.14 setting.

1330//47000=(1330*47000)/(1330+47000)=1293.4 10.5*1293.4/(4400+1293.4)=2.38(V) 2.4(V) Therefore, Pr.07.14 should be set to 2.4.

 

 

resistor value (Ω)

 

 

 

 

1330

 

 

 

 

 

550

 

 

 

 

 

 

 

 

 

 

 

 

Tr

temperature ()

 

 

 

Tr-5Tr+5

07.15

Motor PTC Overheat Warning Level

 

Unit: 0.1

 

Settings

0.1~10.0V

 

Factory Setting: 1.2

 

 

 

 

07.16

Motor PTC Overheat Reset Delta Level

 

Unit: 0.1

 

Settings

0.1~5.0V

 

Factory Setting: 0.6

07.17Treatment of the motor PTC Overheat

Factory Setting: 0

Settings

0

Warn and RAMP to stop

 

1

Warn and COAST to stop

 

2

Warn and keep running

4-100