Chapter 4 Parameters

Therefore, the distance = revolution numbers X circumference = 175 X 2π r It also means that the motor will stop to the original position after 175 circles.

Example 2:

Assume that motor speed is 1.5Hz, the delay time at 10Hz is 10 sec (Pr.01.21=10) and the deceleration time from 60Hz to 0Hz is 40 seconds.

The delay time at 1.5Hz is 1.5 sec and the deceleration from 1.5Hz to 0Hz is 1 sec. The rotation speed n = 120 X 1.5 /4 (rpm/min) = 1.5/2 rpm/sec = 0.75 rpm/sec The revolution numbers = (1.5/2X (1.5+2.5))/2 = 1.5 (revolutions)

f(Hz)

1.5

MI=25 1.5sec 1sec

t

Therefore, the distance = revolution numbers X circumference = 1.5 X 2π r

It also means that the motor will stop after running 1.5 circles.

01.26

 

Maximum Voltage Frequency (Fbase) (Motor 1)

Unit: 0.01

 

 

Settings

0.10 to 600.0Hz

Factory Setting: 60.00

 

 

 

 

01.27

 

Maximum Output Voltage (Vmax) (Motor 1)

Unit: 0.1

 

 

Settings

115V/230V series

0.1 to 255.0V

Factory Setting: 220.0

 

 

 

460V series

0.1 to 510.0V

Factory Setting: 440.0

 

 

 

 

01.28

 

Mid-Point Frequency (Fmid) (Motor 1)

Unit: 0.01

 

 

Settings

0.10 to 600.0Hz

 

Factory Setting: 1.50

 

 

 

 

01.29

 

Mid-Point Voltage (Vmid) (Motor 1)

Unit: 0.1

 

 

Settings

115V/230V series

0.1 to 255.0V

Factory Setting: 10.0

 

 

 

460V series

0.1 to 510.0V

Factory Setting: 20.0

 

 

 

 

 

01.30

Minimum Output Frequency (Fmin) (Motor 1)

Unit: 0.01

 

 

Settings

0.10 to 600.0Hz

 

Factory Setting: 1.50

 

 

01.31

 

Minimum Output Voltage (Vmin) (Motor 1)

Unit: 0.1

 

 

Settings

115V/230V series 0.1 to 255.0V

Factory Setting: 10.0

 

 

 

460V series

0.1 to 510.0V

Factory Setting: 20.0

01.32

Maximum Voltage Frequency (Fbase) (Motor 2)

Unit: 0.01

 

 

Settings

0.10 to 600.0Hz

Factory Setting: 60.00

 

 

 

 

01.33

 

Maximum Output Voltage (Vmax) (Motor 2)

Unit: 0.1

 

 

Settings

115V/230V series

0.1 to 255.0V

Factory Setting: 220.0

Revision June 2008, 04EE, SW--PW V1.11/CTL V2.11

4-49