Delta Electronics VFD-E manual Operation mode indication

Models: VFD-E

1 363
Download 363 pages 22.75 Kb
Page 62
Image 62

 

 

Chapter 4 Parameters

 

Parameter

Explanation

Settings

Factory

Customer

Setting

 

The Selections for

0: Save Keypad & Communication

 

 

 

Frequency

 

 

 

Saving Keypad or

1: Save Keypad Frequency only

0

 

02.13

Communication

 

 

Frequency

 

 

 

 

Command

2: Save Communication Frequency only

 

 

 

 

 

 

 

 

 

 

 

 

Initial Frequency

0: by Current Freq Command

 

 

02.14

Selection (for

1: by Zero Freq Command

0

 

keypad &

 

 

 

 

 

 

RS485/USB)

2: by Frequency Display at Stop

 

 

 

 

 

 

 

 

 

 

 

02.15

Initial Frequency

0.00 ~ 600.0Hz

60.00

 

Setpoint (for keypad

 

 

& RS485/USB)

 

 

 

 

 

 

 

 

 

 

Read Only

 

 

 

Display the Master

Bit0=1: by First Freq Source (Pr.02.00)

 

 

02.16

Bit1=1: by Second Freq Source (Pr.02.09)

##

 

Freq Command

 

Bit2=1: by Multi-input function

 

 

Source

 

 

 

 

Bit3=1: by PLC Freq command (NOT for

 

 

 

 

VFD*E*C models)

 

 

 

 

 

 

 

 

 

Read Only

 

 

 

 

Bit0=1: by Digital Keypad

 

 

 

Display the

Bit1=1: by RS485 communication

 

 

02.17

Operation

Bit2=1: by External Terminal 2/3 wire mode

##

 

 

Command Source

Bit3=1: by Multi-input function

 

 

 

 

 

 

 

 

Bit4=1: by PLC Operation Command (NOT

 

 

 

 

for VFD*E*C models)

 

 

 

 

 

 

 

Group 3 Output Function Parameters

 

 

 

 

 

 

 

Parameter

Explanation

Settings

Factory

Customer

Setting

 

 

0: No function

8

 

03.00

Multi-function

1: AC drive operational

 

 

Output Relay (RA1,

2: Master frequency attained

 

 

 

RB1, RC1)

 

 

 

 

3: Zero speed

 

 

 

 

 

 

 

 

 

4: Over torque detection

1

 

03.01

Multi-function

5: Base-Block (B.B.) indication

 

 

Output Terminal

6: Low-voltage indication

 

 

 

MO1

 

 

 

 

7: Operation mode indication

 

 

 

 

 

 

 

Revision June 2008, 04EE, SW--PW V1.11/CTL V2.11

4-9

Page 62
Image 62
Delta Electronics VFD-E manual Operation mode indication