Chapter 4 Parameters

 

 

13.04

Integral Gain ( I )

Unit: 0.01

 

 

 

 

 

Settings

0.00 to 100.00 sec

Factory Setting: 1.00

0.00Disable

This parameter specifies integral control and associated gain (I), and is used for speed control with PG feedback.

13.05

Speed Control Output Frequency Limit

Unit: 0.01

 

 

 

 

 

Settings

0.00 to 100.00Hz

Factory Setting: 10.00

 

 

 

 

This parameter limits the amount of correction by the PI control on the output frequency when controlling speed via PG feedback. It can limit the maximum output frequency.

 

Frequency

 

 

 

 

 

 

 

 

 

 

 

 

 

output frequency

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

command

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

+

 

 

 

P

 

 

 

 

 

 

 

 

 

Output

 

+

 

 

 

Speed

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

-

 

 

 

+

 

 

 

 

Frequency

 

 

 

 

 

 

detection

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Limit

 

 

 

 

 

 

 

13.03

 

 

+

13.05

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

I

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13.04

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13.06

Speed Feedback Display Filter

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Unit: 1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Settings

0 to 9999 (*2ms)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Factory Setting: 500

 

 

 

When Pr.0.04 is set to 14, its display will be updated regularly. This update time is set by

Pr.13.06.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13.09

Speed Feedback Filter

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Unit: 1

 

Settings

0 to 9999 (*2ms)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Factory Setting: 16

 

 

 

This parameter is the filter time from the speed feedback to the PG card.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13.07

Time for Feedback Signal Fault

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Unit: 0.1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Settings

0.1 to 10.0 sec

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Factory Setting: 1.0

0.0Disabled

This parameter defines the time during which the PID feedback must be abnormal before a warning (see Pr.13.08) is given. It also can be modified according to the system feedback signal time.

If this parameter is set to 0.0, the system would not detect any abnormality signal.

4-150

Revision June 2008, 04EE, SW--PW V1.11/CTL V2.11

Page 203