Image 63

Chapter 4 Parameters

Parameter

Explanation

Settings

Factory

Customer

Setting

 

 

8: Fault indication

 

 

 

 

9: Desired frequency 1 attained

 

 

 

 

10: Terminal count value attained

 

 

 

 

11: Preliminary count value attained

 

 

 

 

12: Over Voltage Stall supervision

 

 

 

 

 

 

 

 

13: Over Current Stall supervision

 

 

 

 

14: Heat sink overheat warning

 

 

 

 

15: Over Voltage supervision

 

 

 

 

16: PID supervision

 

 

 

 

17: Forward command

 

 

 

 

18: Reverse command

 

 

 

 

19: Zero speed output signal

 

 

 

 

20: Warning(FbE,Cexx, AoL2, AUE, SAvE)

 

 

 

 

21: Brake control (Desired frequency

 

 

 

 

attained)

 

 

 

 

22: Drive ready

 

 

 

 

23: Desired frequency 2 attained

 

 

 

 

 

 

 

03.02

Desired Frequency

0.00 to 600.0Hz

0.00

 

 

1 Attained

 

 

 

 

 

 

 

 

03.03

Analog Output

0: Analog frequency meter

0

 

Signal Selection

1: Analog current meter

 

 

(AFM)

 

 

 

 

 

 

 

 

 

 

 

03.04

Analog Output Gain

1 to 200%

100

 

 

 

 

 

 

03.05

Terminal Count

0 to 9999

0

 

 

Value

 

 

 

 

 

 

 

 

03.06

Preliminary Count

0 to 9999

0

 

Value

 

 

 

 

 

 

 

 

 

 

 

EF Active When

0: Terminal count value attained, no EF

 

 

 

display

0

 

03.07

Terminal Count

 

 

 

 

Value Attained

1: Terminal count value attained, EF active

 

 

 

 

 

 

 

 

 

 

 

03.08

Fan Control

0: Fan always ON

0

 

 

 

1: 1 minute after AC motor drive stops, fan

 

 

 

 

will be OFF

 

 

 

 

2: Fan ON when AC motor drive runs, fan

 

 

 

 

OFF when AC motor drive stops

 

 

 

 

 

 

 

4-10

Revision June 2008, 04EE, SW--PW V1.11/CTL V2.11

Page 63