Page 110
Image 110

MI1-DCM (close)

Pr.02.01=0 RUN

output frequency Pr.02.05=0 or 2

Change operation command source

output frequency Pr.02.05=1 or 3

ON

RUN

STO P

OFF

STOP

Pr.02.01=1 or 2

Chapter 4 Parameters

This action will follow MI1/DCM or MI2/DCM status

(ON is close/OFF is open)

When the operation command source isn’t from the external terminals, independently from whether the AC motor drive runs or stops, the AC motor drive will operate according to Pr.02.05 if the two conditions below are both met.

1.When operation command source is changed to external terminal (Pr.02.01=1 or 2)

2.The status of terminal and AC motor drive is different.

And the operation of the AC motor drive will be:

1.When setting 0 or 1, the status of AC motor drive is not changed by the terminal status.

2.When setting 2 or 3, the status of AC motor drive is changed by the terminal status.

MI1-DCM (close)

 

 

 

 

ON

OFF ON

 

 

OFF

 

 

 

 

power is applied

ON

 

 

 

 

 

 

 

 

output frequency

Pr.02.05=0 or 1 it will run

output frequency Pr.02.05=2 or 3

it won't run

when power is applied It needs to received a run command after previous command is cancelled

The Line Start Lockout feature does not guarantee that the motor will never start under this condition. It is possible the motor may be set in motion by a malfunctioning switch.

Revision June 2008, 04EE, SW--PW V1.11/CTL V2.11

4-57