Delta Electronics VFD-E manual Start, End

Models: VFD-E

1 363
Download 363 pages 22.75 Kb
Page 169
Image 169

Chapter 4 Parameters

 

LRC CHK Hi

LRC check sum:

 

 

8-bit check sum consists of 2 ASCII codes

 

LRC CHK Lo

 

 

 

 

 

 

END Hi

End characters:

 

 

END1= CR (0DH), END0= LF(0AH)

 

END Lo

 

 

 

 

 

RTU mode:

 

 

 

 

 

START

A silent interval of more than 10 ms

 

 

 

 

Address

Communication address: 8-bit address

 

 

 

 

Function

Command code: 8-bit command

 

 

 

 

DATA (n-1)

Contents of data:

 

to

 

n×8-bit data, n<=40 (20 x 16-bit data)

 

DATA 0

 

 

 

 

 

 

CRC CHK Low

CRC check sum:

 

CRC CHK High

16-bit check sum consists of 2 8-bit characters

 

 

 

 

END

A silent interval of more than 10 ms

 

 

 

3.2 Address (Communication Address)

Valid communication addresses are in the range of 0 to 254. A communication address equal to 0, means broadcast to all AC drives (AMD). In this case, the AMD will not reply any message to the master device.

00H: broadcast to all AC drives

01H: AC drive of address 01

0FH: AC drive of address 15

10H: AC drive of address 16

:

FEH: AC drive of address 254

For example, communication to AMD with address 16 decimal (10H): ASCII mode: Address=’1’,’0’ => ‘1’=31H, ‘0’=30H

RTU mode: Address=10H

3.3Function (Function code) and DATA (data characters) The format of data characters depends on the function code. 03H: read data from register

06H: write single register

08H: loop detection

4-116

Revision June 2008, 04EE, SW--PW V1.11/CTL V2.11

Page 169
Image 169
Delta Electronics VFD-E manual Start, End