Chapter 2 Installation and Wiring

The position of the control terminals

 

 

 

 

 

RA

RB

RC

 

 

 

 

AFM MCM MO1

 

 

 

 

 

 

 

 

RS-485

MI1

MI2 MI3

MI4

MI5

MI6 DCM DCM 24V ACM AVI

ACI 10V

 

 

Terminal symbols and functions

 

 

Terminal

Terminal Function

 

Factory Settings (NPN mode)

 

 

 

Symbol

 

ON: Connect to DCM

 

 

 

 

 

 

 

 

MI1

Forward-Stop command

ON:

Run in MI1 direction

 

 

OFF:

Stop acc. to Stop Method

 

 

 

 

 

 

 

 

 

 

 

 

MI2

Reverse-Stop command

ON:

Run in MI2 direction

 

 

OFF:

Stop acc. to Stop Method

 

 

 

 

 

 

 

 

 

 

 

 

 

MI3

Multi-function Input 3

Refer to Pr.04.05 to Pr.04.08 for programming the

 

 

 

 

 

 

MI4

Multi-function Input 4

 

 

Multi-function Inputs.

 

 

MI5

Multi-function Input 5

ON: the activation current is 5.5mA.

 

 

OFF: leakage current tolerance is 10μA.

 

 

 

 

 

 

MI6

Multi-function Input 6

 

 

 

 

 

 

 

 

 

 

+24V

DC Voltage Source

+24VDC, 20mA used for PNP mode.

 

 

 

 

 

 

 

DCM

Digital Signal Common

Common for digital inputs and used for NPN

 

 

mode.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RA

Multi-function Relay output

Resistive Load:

 

 

 

 

 

 

 

(N.O.) a

5A(N.O.)/3A(N.C.) 240VAC

 

 

 

 

 

 

 

5A(N.O.)/3A(N.C.) 24VDC

 

 

 

Multi-function Relay output

 

 

RB

Inductive Load:

 

 

(N.C.) b

1.5A(N.O.)/0.5A(N.C.) 240VAC

 

 

 

 

 

 

 

 

 

 

 

1.5A(N.O.)/0.5A(N.C.) 24VDC

 

 

RC

Multi-function Relay common

 

 

Refer to Pr.03.00 for programming

 

 

 

 

 

 

 

 

 

 

 

2-18

Revision June 2008, 04EE, SW--PW V1.11/CTL V2.11