Chapter 4 Parameters

Weights

 

 

 

 

 

 

0=external terminal

Bit

5

4

3

2

1

0

1=internal terminal

MI1

 

 

 

 

 

 

 

MI2

 

 

 

 

 

 

 

MI3

 

 

 

 

 

 

 

MI4

 

 

 

 

 

 

 

MI5

 

 

 

 

 

 

 

MI6

The Setting method is convert binary number to decimal number for input.

For example: if setting MI3, MI5, MI6 to be internal terminals and MI1, MI2, MI4 to be external terminals. The setting value should be bit5X25+bit4X24+bit2X22= 1X25+1X24+1X22= 32+16+4=52 as shown in the following.

Weights

 

 

 

 

 

 

0=external terminal

 

 

 

 

 

 

1=internal terminal

Bit

1

1

0

1

0

0

MI1

MI2

MI3

MI4

MI5

MI6

When extension card is installed, the number of the multi-function input terminals will increase according to the extension card. The maximum number of the multi-function input terminals is shown as follows.

 

 

 

 

 

 

 

 

 

 

 

 

 

0=external terminal

 

Weights

 

 

 

 

 

 

 

 

 

 

1=internal terminal

 

Bit

11 10

9

8

7

6

5

4

3

2

1

0

MI1

 

 

 

 

 

 

 

 

 

 

 

 

 

MI2

 

 

 

 

 

 

 

 

 

 

 

 

 

MI3

 

 

 

 

 

 

 

 

 

 

 

 

 

MI4

 

 

 

 

 

 

 

 

 

 

 

 

 

MI5

 

 

 

 

 

 

 

 

 

 

 

 

 

MI6

 

 

 

 

 

 

 

 

 

 

 

 

 

MI7

 

 

 

 

 

 

 

 

 

 

 

 

 

MI8

 

 

 

 

 

 

 

 

 

 

 

 

 

MI9

 

 

 

 

 

 

 

 

 

 

 

 

 

MI10

 

 

 

 

 

 

 

 

 

 

 

 

 

MI11

 

 

 

 

 

 

 

 

 

 

 

 

 

MI12

04.28

Internal Terminal Status

 

 

 

 

 

 

 

 

 

 

Unit: 1

 

Settings

0 to 4095

 

 

 

 

 

 

 

 

 

 

Factory Setting: 0

This parameter is used to set the internal terminal action via keypad, communication or PLC.

4-86