Delta Electronics VFD-E manual Over-current stall prevention during operation, 06.04, 06.05

Models: VFD-E

1 363
Download 363 pages 22.75 Kb
Page 145
Image 145

Chapter 4 Parameters

Over-Current Stall

 

Over-Current

Prevention during

Operation, output

Detection

frequency decrease

Level

Output Current

06.02

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Output

 

 

 

Frequency

over-current stall prevention during operation

06.03Over-Torque Detection Mode (OL2)

 

 

Factory Setting: 0

Settings

0

Over-Torque detection disabled.

 

1

Over-Torque detection enabled during constant speed operation.

 

 

After over-torque is detected, keep running until OL1 or OL occurs.

 

2

Over-Torque detection enabled during constant speed operation.

 

 

After over-torque is detected, stop running.

 

3

Over-Torque detection enabled during acceleration. After over-

 

 

torque is detected, keep running until OL1 or OL occurs.

 

4

Over-Torque detection enabled during acceleration. After over-

 

 

torque is detected, stop running.

This parameter determines the operation mode of the drive after the over-torque (OL2) is

detected via the following method: if the output current exceeds the over-torque detection level

(Pr.06.04) longer than the setting of Pr.06.05 Over-Torque Detection Time, the warning

message “OL2” is displayed. If a Multi-functional Output Terminal is set to over-torque

detection (Pr.03.00~03.01=04), the output is on. Please refer to Pr.03.00~03.01 for details.

06.04

Over-Torque Detection Level (OL2)

Unit: 1

 

Settings

10 to 200%

Factory Setting: 150

 

 

 

 

This setting is proportional to the Rated Output Current of the drive.

06.05

Over-Torque Detection Time (OL2)

Unit: 0.1

 

Settings

0.1 to 60.0 sec

Factory Setting: 0.1

 

 

 

 

4-92

Revision June 2008, 04EE, SW--PW V1.11/CTL V2.11

Page 145