Appendix B Accessories

B.10.2.1 Introduction

Device CME-LW01 is used for communication interface between Modbus and LonTalk. CME- LW01 needs be configured via LonWorks network tool first, so that it can perform the function on LonWorks network. No need to set CME-LW01 address.

This manual provides instructions for the installation and setup for CME-LW01 that is used to communicate with Delta VFD-E (firmware version of VFD-E should conform with CME-LW01 according to the table below) via LonWorks Network.

B.10.2.2 Dimensions

72.2 [2.84]

59.7 [2.35]

9.5 [0.37]

SP

CME-LW 01

57.3 [2.26]

34.8 [1.37]

3.5 [0.14]

B.10.2.3 Specifications

Power supply: 16-30VDC, 750mW

Communication:

Modbus in ASCII format, protocol: 9600, 7, N, 2

LonTalk:

free topology with FTT-10A 78 Kbps.

LonTalk terminal:

4-pin terminals, wire gauge: 28-12 AWG, wire strip length: 7-8mm

RS-485 port: 8 pins with RJ-45

Revision June 2008, 04EE, SW--PW V1.11/CTL V2.11