Chapter 4 Parameters

04.26Display the Status of Multi-function Input Terminal

Settings

Read Only

Factory setting: ##

Display

Bit0: MI1 Status

 

 

Bit1: MI2 Status

 

 

Bit2: MI3 Status

 

 

Bit3: MI4 Status

 

 

Bit4: MI5 Status

 

 

Bit5: MI6 Status

 

 

Bit6: MI7 Status

 

 

Bit7: MI8 Status

 

 

Bit8: MI9 Status

 

 

Bit9: MI10 Status

 

 

Bit10: MI11 Status

 

 

Bit11: MI12 Status

 

 

 

 

The multi-function input terminals are falling-edge triggered. For standard AC motor drive (without extension card), there are MI1 to MI6 and Pr.04.26 will display 63 (111111) for no action.

Weights

 

 

 

 

 

 

0=Active

Bit

5

4

3

2

1

0

1=off

MI1

 

 

 

 

 

 

 

MI2

 

 

 

 

 

 

 

MI3

 

 

 

 

 

 

 

MI4

 

 

 

 

 

 

 

MI5

MI6

For Example:

If Pr.04.26 displays 52, it means MI1, MI2 and MI4 are active.

The display value 52= 32+16+4 =1 X 25+ 1X 24 + 1X 22 = bit 6 X 25+ bit 5 X 24 + bit 3 X 22

4-84

Revision June 2008, 04EE, SW--PW V1.11/CTL V2.11