Delta Electronics VFD-E manual Example 3 Use of bias and gain for use of full range

Models: VFD-E

1 363
Download 363 pages 22.75 Kb
Page 123
Image 123

Chapter 4 Parameters

 

 

 

 

60Hz

 

 

Pr.01.00=60Hz--Max. output Freq.

 

 

Potentiometer

40Hz

 

 

Pr.04.00

=16.7%--Bias adjustment

 

 

Pr.04.01

=0--Positive bias

 

 

 

 

 

 

 

 

Pr.04.02

=100%--Input gain

Bias 10Hz

 

 

 

 

Pr.04.03 =0--No negative bias command

 

 

 

Gain:100%

Adjustment

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0Hz 0V

5V

10V Bias adjustment:((10Hz/60Hz)/(Gain/100%))*100%=16.7%

Example 3: Use of bias and gain for use of full range

This example also shows a popular method. The whole scale of the potentiometer can be used as desired. In addition to signals of 0 to 10V, the popular voltage signals also include signals of 0 to 5V, or any value under 10V. Regarding the setting, please refer to the following examples.

 

60Hz

 

 

Pr.01.00=60Hz--Max. output Freq.

 

 

 

Potentiometer

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Pr.04.00

=20.0%--Bias adjustment

 

 

 

 

 

 

 

 

 

Pr.04.01

=0--Positive bias

 

 

 

 

 

 

 

 

 

Pr.04.02

=83.3%--Input gain

 

10Hz

 

 

Pr.04.03 =0--No negative bias command

Bias

 

 

Gain:(10V/(10V+2V))*100%=83.3%

Adjustment

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

-2V0Hz0V

5V

10V Bias adjustment:((10Hz/60Hz)/(Gain/100%))*100%=20.0%

 

XV

 

 

 

 

Example 4: Use of 0-5V potentiometer range via gain adjustment

This example shows a potentiometer range of 0 to 5 Volts. Instead of adjusting gain as example

below, you can set Pr. 01.00 to 120Hz to achieve the same results.

Gain adjustment

60Hz

30Hz

0Hz 0V

5V

10V

Pr.01.00=60Hz--Max. output Freq. Potentiometer

Pr.04.00 =0.0%--Bias adjustment Pr.04.01 =0--Positive bias Pr.04.02 =200%--Input gain

Pr.04.03 =0--No negative bias command Gain:(10V/5V)*100%=200%

4-70

Revision June 2008, 04EE, SW--PW V1.11/CTL V2.11

Page 123
Image 123
Delta Electronics VFD-E manual Example 3 Use of bias and gain for use of full range