Chapter 4 Parameters

 

 

 

 

03.11

Brake Release Frequency

 

Unit: 0.01

 

Settings

0.00 to 600.0Hz

 

Factory Setting: 0.00

 

 

 

 

03.12

Brake Engage Frequency

 

Unit: 0.01

 

Settings

0.00 to 600.0Hz

 

Factory Setting: 0.00

 

 

 

 

 

These two parameters are used to set control of mechanical brake via the output terminals (Relay or MO1) when Pr.03.00~03.01 is set to 21. Refer to the following example for details. Example:

1.Case 1: Pr.03.12 Pr.03.11

2.Case 2: Pr.03.12 Pr.03.11

Frequency

Output

Case 1: Pr.03.12

Pr. 03.11

Case 2: Pr.03.12

Time

Run/Stop

Case 1: MO1=21

Case 2: MO1=21

Note: MO1: setting value of Pr.03.01

03.13Display the Status of Multi-function Output Terminals

Settings Read Only

Factory setting: ##

Bit0: RLY Status

 

Bit1: MO1 Status

 

Bit2: MO2/RA2 Status

 

Bit3: MO3/RA3 Status

 

Bit4: MO4/RA4 Status

 

Bit5: MO5/RA5 Status

 