Delta Electronics VFD-E manual Fault Fault Descriptions Corrective Actions Name

Models: VFD-E

1 363
Download 363 pages 22.75 Kb
Page 226
Image 226

 

 

 

Chapter 6 Fault Code Information and Maintenance

 

Fault

Fault Descriptions

 

 

Corrective Actions

 

 

Name

 

 

 

 

 

 

 

 

 

 

 

CANopen Heartbeat Time out

 

Connect to CAN bus again and reset CAN bus

 

 

 

 

 

 

 

 

Only for VFDxxxExxC

 

 

 

 

 

 

 

 

 

 

 

CANopen SYNC Time out

 

Check if CANopen synchronous message is

 

 

 

abnormal

 

 

Only for VFDxxxExxC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CANopen SDO Time out

 

Check if command channels are full

 

 

 

 

 

 

 

 

Only for VFDxxxExxC

 

 

 

 

 

 

 

 

 

 

 

 

CANopen SDO buffer

 

1.

Too short time between commands, please

 

 

 

 

check SDO message sent from the master

 

 

overflowOnly for

 

 

 

 

 

2.

Reset CAN bus

 

 

VFDxxxExxC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CAN bus offOnly for

 

1.

Check if it connects to terminal resistor

 

 

 

2.

Check if the signal is abnormal

 

 

VFDxxxExxC

 

 

 

 

3.

Check if the master is connected

 

 

 

 

 

 

CAN Boot up faultOnly for

 

1.

Check if the master is connected

 

 

 

2.

Reset CAN bus

 

 

VFDxxxExxC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Error communication protocol

 

Check if the communication protocol is correct

 

 

 

 

 

 

 

 

of CANopen Only for

 

 

 

 

 

 

VFDxxxExxC

 

 

 

 

 

 

 

 

 

 

 

Revision June 2008, 04EE, SW--PW V1.11/CTL V2.11

6-5

Page 226
Image 226
Delta Electronics VFD-E manual Fault Fault Descriptions Corrective Actions Name