Delta Electronics VFD-E manual Special Auxiliary Relays

Models: VFD-E

1 363
Download 363 pages 22.75 Kb
Page 308
Image 308

 

 

Appendix D How to Use PLC Function

D.4.8 Special Auxiliary Relays

 

 

 

 

 

 

 

 

Special

Function

Read(R)/

 

 

M

Write(W)

 

 

 

 

 

 

 

 

 

 

M1000

Normally open contact (a contact). This contact is On when running and it is

R

 

On when the status is set to RUN.

 

 

 

 

 

 

 

 

 

 

M1001

Normally closed contact (b contact). This contact is Off in running and it is Off

R

 

when the status is set to RUN.

 

 

 

 

 

 

 

 

 

 

M1002

On only for 1 scan after RUN. Initial pulse is contact a. It will get positive

R

 

pulse in the RUN moment. Pulse width=scan period.

 

 

 

 

 

 

 

 

 

 

M1003

Off only for 1 scan after RUN. Initial pulse is contact a. It will get negative

R

 

pulse in the RUN moment. Pulse width=scan period.

 

 

 

 

 

 

 

 

 

 

M1004

Reserved

--

 

 

 

 

 

 

M1005

Fault indication of the AC motor drives

R

 

 

 

 

 

M1006

Output frequency is 0

R

 

 

 

 

 

M1007

The operation direction of AC motor drives (FWD: 0, REV: 1)

R

 

 

 

 

 

 

M1008

Reserved

--

 

 

 

 

 

 

 

M1009

Reserved

--

 

 

 

 

 

 

 

M1010

Reserved

--

 

 

 

 

 

 

M1011

10ms clock pulse, 5ms On/5ms Off

R

 

 

 

 

 

M1012

100ms clock pulse, 50ms On / 50ms Off

R

 

 

 

 

 

M1013

1s clock pulse, 0.5s On / 0.5s Off

R

 

 

 

 

 

M1014

1min clock pulse, 30s On / 30s Off

R

 

 

 

 

 

M1015

Frequency attained

R

 

 

 

 

 

M1016

Parameter read/write error

R

 

 

 

 

 

M1017

Succeed to write parameter

R

 

 

 

 

 

M1018

Enable high-speed counter function (When M1028=On)

R

 

 

 

 

 

M1019

Reserved

R

 

 

 

 

 

M1020

Zero flag

R

 

 

 

 

 

M1021

Borrow flag

R

 

 

 

 

 

M1022

Carry flag

R

 

 

 

 

 

M1023

Divisor is 0

R

 

 

 

 

 

 

M1024

Reserved

--

 

 

 

 

 

 

M1025

RUN(ON) / STOP(OFF) the AC motor drive

R/W

 

 

 

 

 

Revision June 2008, 04EE, SW--PW V1.11/CTL V2.11