Chapter 4 Parameters

Group 8: Special Parameters

 

 

 

 

08.00

DC Brake Current Level

Unit: 1

 

Settings

0 to 100%

Factory Setting: 0

 

 

 

 

This parameter sets the level of DC Brake Current output to the motor during start-up and stopping. When setting DC Brake Current, the Rated Current (Pr.00.01) is regarded as 100%. It is recommended to start with a low DC Brake Current Level and then increase until proper holding torque has been achieved.

08.01

DC Brake Time during Start-up

Unit: 0.1

 

Settings

0.0 to 60.0 sec

Factory Setting: 0.0

 

 

 

 

This parameter determines the duration of the DC Brake current after a RUN command. When the time has elapsed, the AC motor drive will start accelerating from the Minimum Frequency (Pr.01.05).

08.02

DC Brake Time during Stopping

Unit: 0.1

 

Settings

0.0 to 60.0 sec

Factory Setting: 0.0

 

 

 

 

This parameter determines the duration of the DC Brake current during stopping. If stopping with DC Brake is desired, Pr.02.02 Stop Method must be set to 0 or 2 for Ramp to Stop.

08.03

Start-Point for DC Brake

Unit: 0.01

 

Settings

0.00 to 600.0Hz

Factory Setting: 0.00

This parameter determines the frequency when DC Brake will begin during deceleration.

 

Output Frequency

 

 

 

Start-Point for

DC Braking Time

 

 

DC Braking

 

 

Time during

during Stopping

01.05Stopping08.03 Minimum Output

Frequency

Run/Stop

ONOFF