Delta Electronics VFD-E manual Revision June 2008, 04EE, SW--PW V1.11/CTL 123

Models: VFD-E

1 363
Download 363 pages 22.75 Kb
Page 176
Image 176

Chapter 4 Parameters

Unsigned int crc_chk(unsigned char* data, unsigned char length){ int j;

unsigned int reg_crc=0xFFFF; while(length--){

reg_crc ^= *data++; for(j=0;j<8;j++){

if(reg_crc & 0x01){ /* LSB(b0)=1 */ reg_crc=(reg_crc>>1) ^ 0xA001;

}else{ reg_crc=reg_crc >>1;

}

}

}

return reg_crc;

}

3.5 Address list

The contents of available addresses are shown as below:

Content

AC drive

Parameters

Command Write only

Address

Function

GGmeans parameter group, nn means parameter number, for example, the address of Pr 04.01 is 0401H. Refer to

GGnnH chapter 5 for the function of each parameter. When reading

 

parameter by command code 03H, only one parameter can

 

be read at one time.

 

 

 

 

 

00B: No function

 

Bit 0-1

01B: Stop

 

10B: Run

 

 

 

 

11B: Jog + Run

 

 

 

 

Bit 2-3

Reserved

 

 

 

2000H

00B: No function

01B: FWD

 

Bit 4-5

 

10B: REV

 

 

 

 

11B: Change direction

 

 

 

 

Bit 6-7

00B: Comm. forced 1st accel/decel

 

01B: Comm. forced 2nd accel/decel

 

 

 

 

 

 

Bit 8-15

Reserved

 

 

 

Revision June 2008, 04EE, SW--PW V1.11/CTL V2.11

4-123

Page 176
Image 176
Delta Electronics VFD-E manual Revision June 2008, 04EE, SW--PW V1.11/CTL 123