Delta Electronics VFD-E manual Revision June 2008, 04EE, SW--PW V1.11/CTL 153

Models: VFD-E

1 363
Download 363 pages 22.75 Kb
Page 206
Image 206

 

 

 

Chapter 4 Parameters

 

Parameter

Explanation

Settings

Factory

Customer

Setting

8:Display the estimated value of torque as it relates to current (t)

9:Display AVI (I) (V)

10:Display ACI / AVI2 (i) (mA/V)

11:Display the temperature of IGBT (h) (°C)

12:Display AVI3/ACI2 level (I.)

13:Display AVI4/ACI3 level (i.)

14:Display PG speed in RPM (G)

15:Display motor number (M)

Group 1 Basic Parameters

Parameter

Explanation

Settings

Factory

Customer

 

 

 

Setting

 

01.11

Accel Time 2

0.1 to 600.0 / 0.01 to 600.0 sec

1.0

 

 

 

 

 

 

01.12

Decel Time 2

0.1 to 600.0 / 0.01 to 600.0 sec

1.0

 

 

 

 

 

 

Group 2 Operation Method Parameters

 

 

 

 

 

 

 

Parameter

Explanation

Settings

Factory

Customer

Setting

 

 

0: Digital keypad UP/DOWN keys or Multi-

 

 

 

 

function Inputs UP/DOWN. Last used

 

 

 

 

frequency saved.

 

 

02.00

Source of First

1: 0 to +10V from AVI

5

 

Master Frequency

2: 4 to 20mA from ACI or 0 to +10V from

 

 

Command

 

 

 

AVI2

 

 

 

 

 

 

 

 

3: RS-485 (RJ-45)/USB communication

 

 

 

 

4: Digital keypad potentiometer

 

 

 

 

5: CANopen communication

 

 

 

 

 

 

 

02.01

Source of First

0: Digital keypad

5

 

 

Operation

1: External terminals. Keypad STOP/RESET

 

 

 

Command

 

 

 

 

enabled.

 

 

 

 

2: External terminals. Keypad STOP/RESET

 

 

 

 

disabled.

 

 

 

 

 

 

 

Revision June 2008, 04EE, SW--PW V1.11/CTL V2.11

4-153