Chapter 4 Parameters

4.1 Summary of Parameter Settings

: The parameter can be set during operation.

Group 0 User Parameters

Parameter

Explanation

Settings

Factory

Customer

Setting

00.00

Identity Code of the

Read-only

##

 

 

AC motor drive

 

 

 

 

 

 

 

 

00.01

Rated Current

Read-only

#.#

 

 

Display of the AC

 

 

 

 

motor drive

 

 

 

 

 

 

 

 

 

 

0: Parameter can be read/written

 

 

 

 

1: All parameters are read only

 

 

 

 

6: Clear PLC program (NOT for VFD*E*C

 

 

00.02

Parameter Reset

models)

0

 

9: All parameters are reset to factory settings

 

 

 

 

 

 

 

(50Hz, 230V/400V or 220V/380V depends on

 

 

 

 

Pr.00.12)

 

 

 

 

10: All parameters are reset to factory

 

 

 

 

settings (60Hz, 220V/440V)

 

 

 

 

 

 

 

 

 

0: Display the frequency command value

 

 

 

 

(Fxxx)

 

 

 

 

1: Display the actual output frequency (Hxxx)

 

 

 

 

2: Display the content of user-defined unit

 

 

00.03

Start-up Display

(Uxxx)

0

 

Selection

 

 

 

3: Multifunction display, see Pr.00.04

 

 

 

 

 

 

 

 

4: FWD/REV command

 

 

 

 

5: PLCx (PLC selections: PLC0/PLC1/PLC2)

 

 

 

 

(NOT for VFD*E*C models)

 

 

 

 

 

 

 

00.04

Content of Multi-

0: Display the content of user-defined unit

0

 

function Display

(Uxxx)

 

 

 

 

 

 

1: Display the counter value (c)

 

 

 

 

2: Display PLC D1043 value (C) (NOT for

 

 

 

 

VFD*E*C models)

 

 

 

 

3: Display DC-BUS voltage (u)

 

 

 

 

4: Display output voltage (E)

 

 

 

 

 

 

 

4-2

Revision June 2008, 04EE, SW--PW V1.11/CTL V2.11

Page 55
Image 55