Delta Electronics VFD-E manual 01.08, 01.09, 01.10, 01.11, 01.12

Models: VFD-E

1 363
Download 363 pages 22.75 Kb
Page 97
Image 97

Chapter 4 Parameters

01.0801.07

Voltage

Output Frequency

Output Frequency

Lower Limit

Upper Limit

01.02

 

 

 

 

Maximum

 

 

 

 

Output

 

 

 

 

Voltage

 

 

 

 

01.04

 

 

 

 

Mid-point

 

 

 

 

Voltage

 

The limit of

 

 

 

 

 

 

Output

 

 

 

 

Frequency

 

01.06

 

 

Frequency

Minimum

01.05

01.03

01.01

01.00

Output

Minimum

Mid-point

Maximum Voltage

Maximum

Voltage

Output

Freq.

Frequency

Output

 

 

Freq.

 

(Base Frequency)

Frequency

V/f Curve

01.08

Output Frequency Lower Limit

Unit: 0.1

 

Settings

0.0 to 100.0%

Factory Setting: 0.0

 

 

 

 

The Upper/Lower Limits are to prevent operation errors and machine damage.

If the Output Frequency Upper Limit is 50Hz and the Maximum Output Frequency is 60Hz, the Output Frequency will be limited to 50Hz.

If the Output Frequency Lower Limit is 10Hz, and the Minimum Output Frequency (Pr.01.05) is set to 1.0Hz, then any Command Frequency between 1.0-10Hz will generate a 10Hz output from the drive.

This parameter must be equal to or less than the Output Frequency Upper Limit (Pr.01.07). The Output Frequency Lower Limit value = (Pr.01.00 * Pr.01.08) /100.

01.09

Acceleration Time 1 (Taccel 1)

Unit: 0.1/0.01

01.10

Deceleration Time 1 (Tdecel 1)

Unit: 0.1/0.01

01.11

Acceleration Time 2 (Taccel 2)

Unit: 0.1/0.01

01.12

Deceleration Time 2 (Tdecel 2)

Unit: 0.1/0.01

Settings 0.1 to 600.0 sec / 0.01 to 600.0 secFactory Setting: 10.0

Acceleration/deceleration time 1 or 2 can be switched by setting the external terminals MI3~ MI12 to 7 (set Pr.04.05~Pr.04.08 to 7 or Pr.11.06~Pr.11.11 to 7).

01.19 Accel/Decel Time Unit

Factory Setting: 0

Settings

0

Unit: 0.1 sec

 

1

Unit: 0.01 sec

 

 

 

4-44

 

Revision June 2008, 04EE, SW--PW V1.11/CTL V2.11

Page 97
Image 97
Delta Electronics VFD-E manual 01.08, 01.09, 01.10, 01.11, 01.12