Chapter 4 Parameters

Settings

Function

Description

 

 

 

15

PID function

When an input ON with this setting is ON, the PID function will be

disabled

disabled.

 

 

 

 

 

 

AC motor drive will stop output and the motor free run if one of

16

Output Shutoff Stop

these settings is enabled. If the status of terminal is changed, AC

 

 

motor drive will restart from 0Hz.

 

 

 

17

Parameter lock

When this setting is enabled, all parameters will be locked and

enable

write parameters is disabled.

 

 

 

 

 

Operation

ON: Operation command via Ext. Terminals

 

Command

 

OFF: Operation command via Pr.02.01 setting

18

Selection (Pr.02.01

 

setting/external

When the settings 18, 19 and 20 are ON at the same time, the

 

priority should be setting 18 > setting19 > setting20.

 

terminals)

 

 

 

 

 

 

Operation

ON: Operation command via Digital Keypad

 

Command

 

OFF: Operation command via Pr.02.01 setting

19

Selection (Pr 02.01

 

setting/Digital

When the settings 18, 19 and 20 are ON at the same time, the

 

priority should be setting 18 > setting19 > setting20.

 

Keypad)

 

 

 

 

 

 

Operation

ON: Operation command via Communication

 

Command

 

OFF: Operation command via Pr.02.01 setting

20

Selection (Pr 02.01

 

setting/

When the settings 18, 19 and 20 are ON at the same time, the

 

priority should be setting 18 > setting19 > setting20.

 

Communication)

 

 

 

 

 

21

Forward/Reverse

This function has top priority to set the direction for running (If

“Pr.02.04=0”)

 

 

 

 

 

 

Source of second

Used to select the first/second frequency command source. Refer

 

to Pr.02.00 and 02.09.

22

frequency

ON: 2nd Frequency command source

 

command enabled

 

OFF: 1st Frequency command source

 

 

Revision June 2008, 04EE, SW--PW V1.11/CTL V2.11