Chapter 4 Parameters

Bit6: MO6/RA6 Status

Bit7: MO7/RA7 Status

For standard AC motor drive (without extension card), the multi-function output terminals are falling-edge triggered and Pr.03.13 will display 3 (11) for no action.

Weights

 

0=Active

 

1=Off

Bit

1 0

Relay 1

MO1

For Example:

If Pr.03.13 displays 2, it means Relay 1 is active.

The display value 2 =bit 1 X 21

When extension card is installed, the number of the multi-function output terminals will increase according to the extension card. The maximum number of the multi-function output terminals is shown as follows.

0=Active

Weights 1=Off

Bit

7 6 5 4 3 2 1 0

 

Relay 1

 

 

 

 

 

 

 

 

 

 

 

MO1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MO2/RA2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MO3/RA3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MO4/RA4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MO5/RA5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MO6/RA6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MO7/RA7

 

 

 

 

 

 

 

 

 

 

4-68

Revision June 2008, 04EE, SW--PW V1.11/CTL V2.11