Chapter 4 Parameters

 

 

10.06

Primary Delay Filter Time

Unit: 0.1

 

Settings

0.0 to 2.5 sec

Factory Setting: 0.0

 

 

 

 

To avoid amplification of measurement noise in the controller output, a derivative digital filter is inserted. This filter helps to dampen oscillations.

The complete PID diagram is in the following:

+

 

 

 

P

 

 

 

I

 

Integral

+

 

 

 

Output

 

Digital

 

 

 

 

 

 

 

 

 

gain

+

 

 

 

 

Freq.

 

 

Freq.

 

 

 

 

 

 

 

 

 

 

 

 

filter

 

Setpoint

 

 

 

 

 

 

 

 

 

limit

 

 

 

 

 

Limit

 

 

Command

 

 

 

 

 

 

 

 

 

 

 

-

 

 

 

10.02

10.03

10.05

+

 

10.07

10.06

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10.04

 

 

 

 

 

 

 

 

 

 

 

 

 

Input Freq.

 

 

 

PID

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Gain

 

 

 

 

 

 

 

feedback

 

 

 

 

 

 

 

10.10

 

 

 

 

 

 

10.01

 

 

 

 

 

 

 

 

 

 

 

10.07

PID Output Frequency Limit

Unit: 1

 

 

 

 

 

 

 

Settings

0 to 110 %

Factory Setting: 100

 

 

 

 

 

This parameter defines the percentage of output frequency limit during the PID control. The formula is Output Frequency Limit = Maximum Output Frequency (Pr.01.00) X Pr.10.07 %. This parameter will limit the Maximum Output Frequency. An overall limit for the output frequency can be set in Pr.01.07.

10.08

PID Feedback Signal Detection Time

Unit: 0.1

 

 

 

 

 

Settings

0.0 to d 3600 sec

Factory Setting: 60.0

 

 

 

 

This parameter defines the time during which the PID feedback must be abnormal before a warning (see Pr.10.09) is given. It also can be modified according to the system feedback signal time.

If this parameter is set to 0.0, the system would not detect any abnormality signal.

10.09Treatment of the Erroneous Feedback Signals (for PID feedback error)

Factory Setting: 0

Settings

0

Warning and RAMP to stop

 

1

Warning and COAST to stop

 

2

Warning and keep operating

 

 

 

4-134

Revision June 2008, 04EE, SW--PW V1.11/CTL V2.11