Chapter 4 Parameters

When Pr.02.07 is set to 1: increase/decrease the frequency by acceleration/deceleration settings. It is valid only when the AC motor drive is running.

When Pr.02.07 is set to 2: increase/decrease the frequency by Pr.02.08.

When Pr.02.07 is set to 3: increase/decrease the frequency by Pr.02.08 (unit: pulse input).

02.11

Keypad Frequency Command

Unit: 0.01

 

 

 

 

 

Settings

0.00 to 600.0Hz

Factory Setting: 60.00

 

This parameter can be used to set frequency command or read keypad frequency command.

 

 

 

02.12

Communication Frequency Command

Unit: 0.01

 

 

 

 

 

Settings

0.00 to 600.0Hz

Factory Setting: 60.00

This parameter can be used to set frequency command or read communication frequency command.

02.13The Selections for Saving Keypad or Communication Frequency Command

Factory Setting: 0

Settings

0

Save Keypad & Communication Frequency

 

1

Save Keypad Frequency only

 

2

Save Communication Frequency only

 

 

 

This parameter is used to save keypad or RS-485 frequency command.

02.14Initial Frequency Selection (for keypad & RS485/USB)

 

 

 

 

Factory Setting: 0

 

Settings

0

By Current Freq Command

 

 

 

1

By Zero Freq Command

 

 

 

2

By Frequency Display at Stop

 

 

 

 

02.15

Initial Frequency Setpoint (for keypad & RS485/USB)

Unit: 0.01

 

Settings

0.00 ~ 600.0Hz

Factory Setting: 60.00

These parameters are used to determinate the frequency at stop:

When setting Pr.02.14 to 0: the initial frequency will be current frequency.

When setting Pr.02.14 to 1: the initial frequency will be 0.

When setting Pr.02.14 to 2: the initial frequency will be Pr.02.15.

Revision June 2008, 04EE, SW--PW V1.11/CTL V2.11

4-59