Chapter 4 Parameters

Settings

0.1~10.0V

Factory Setting: 2.4

 

 

 

When the motor is running at low frequency for a long time, the cooling function of the motor fan will be lower. To prevent overheating, it needs to have a Positive Temperature Coefficient thermoistor on the motor and connect its output signal to the drive’s corresponding control terminals.

When the source of first/second frequency command is set to AVI (02.00=1/02.09=1), it will disable the function of motor PTC overheat protection (i.e. Pr.07.12 cannot be set to 1).

If temperature exceeds the setting level, motor will be coast to stop and is

displayed. When the temperature decreases below the level of (Pr.07.15-Pr.07.16) and

stops blinking, you can press RESET key to clear the fault.

Pr.07.14 (overheat protection level) must exceed Pr.07.15 (overheat warning level). The PTC uses the AVI-input and is connected via resistor-divider as shown below.

1.The voltage between +10V to ACM: lies within 10.4V~11.2V.

2.The impedance for AVI is around 47kΩ.

3.Recommended value for resistor-divider R1 is 1~20kΩ.

4.Please contact your motor dealer for the curve of temperature and resistance value for PTC.

 

VFD-E

 

+10V

resistor-divider

 

R1

AVI

 

47kΩ

PTC

 

 

ACM

 

internal circuit

Revision June 2008, 04EE, SW--PW V1.11/CTL V2.11