Chapter 4 Parameters

When the AC motor drive is in sleep mode, frequency command is still calculated by PID. When frequency reaches wake up frequency, AC motor drive will accelerate from Pr.01.05 minimum frequency following the V/f curve.

The wake up frequency must be higher than sleep frequency.

Frequency

 

 

 

 

 

frequency calculated by PID

10.16

The limit of

 

 

 

 

 

 

 

 

decel. time

 

 

output

 

 

 

 

 

 

 

frequency

10.15

 

 

 

 

 

 

 

 

 

01.05

 

 

 

 

 

The limit of

 

 

 

 

 

accel. time

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Time

 

 

10.14

 

 

 

 

 

 

 

 

 

 

 

 

Fmin

lower bound

Fsleep

 

 

 

 

 

of frequency

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

lower bound

 

 

 

 

 

Fcmd=0

Fmin<Fsleep< of frequency

 

 

 

 

Fout = 0

When output frequency sleep frequency and time > detection time, it will go in sleep mode. When min. output frequency PID frequency lower bound of frequency and sleep function is enabled (output frequency sleep frequency and time > detection time), frequency will be 0 (in sleep mode). If sleep function is disabled, frequency command = lower bound frequency.

When PID frequency < min. output frequency and sleep function is enabled (output frequency

sleep frequency and time > detection time), output frequency =0 (in sleep mode).

If output frequency sleep frequency but time < detection time, frequency command = lower frequency. If sleep function is disabled, output frequency =0.

4-136

Revision June 2008, 04EE, SW--PW V1.11/CTL V2.11