Chapter 4 Parameters

Content

Address

 

Function

 

 

 

 

 

2001H

Frequency command

 

 

 

 

 

 

Bit 0

1: EF (external fault) on

 

2002H

 

 

 

Bit 1

1: Reset

 

 

 

 

 

 

Bit 2-15

Reserved

 

 

 

 

Status

 

Error code:

 

 

 

 

monitor

2100H

0: No error occurred

Read only

 

 

 

 

1: Over-current (oc)

 

 

 

 

 

 

 

2: Over-voltage (ov)

 

 

 

 

 

3: IGBT Overheat (oH1)

 

 

 

 

 

4: Power Board Overheat (oH2)

 

 

 

 

 

5: Overload (oL)

 

 

 

 

 

6: Overload1 (oL1)

 

 

 

 

 

7: Overload2 (oL2)

 

 

 

 

 

8: External fault (EF)

 

 

 

 

 

9: Current exceeds 2 times rated current during accel (ocA)

 

 

 

 

 

10: Current exceeds 2 times rated current during decel (ocd)

 

 

Current exceeds 2 times rated current during decel (ocd)

 

 

 

 

 

11: Current exceeds 2 times rated current during steady state

 

 

operation (ocn)

 

 

 

 

 

12: Ground Fault (GFF)

 

 

 

 

 

13: Low voltage (Lv)

 

 

 

 

 

14: PHL (Phase-Loss)

 

 

 

 

2100H

15: Base Block

 

 

 

 

 

16: Auto accel/decel failure (cFA)

 

 

 

 

 

17: Software protection enabled (codE)

 

 

 

 

 

18: Power Board CPU WRITE failure (CF1.0)

 

 

 

 

 

19: Power Board CPU READ failure (CF2.0)

 

 

 

 

 

20: CC, OC Hardware protection failure (HPF1)

 

 

 

 

 

21: OV Hardware protection failure (HPF2)

 

 

 

 

 

22: GFF Hardware protection failure (HPF3)

 

 

 

 

 

23: OC Hardware protection failure (HPF4)

4-124

Revision June 2008, 04EE, SW--PW V1.11/CTL V2.11