Appendix D How to Use PLC Function

API

141

 

Mnemonic

 

Operands

Function

 

 

 

 

 

 

 

FPID

 

P

S1, S2, S3, S4

PID control for the AC motor drive

 

 

 

 

 

 

Type

Bit Devices

 

 

Word devices

 

 

Program Steps

OP

X

Y

M

K

H

KnX KnY KnM

T

C

D FPID, FPIDP: 9 steps

 

S1

 

 

 

*

*

 

 

 

*

S2

 

 

 

*

*

 

 

 

*

S3

 

 

 

*

*

 

 

 

*

S4

 

 

 

*

*

 

 

 

*

Operands:

S1: PID Set Point Selection(0-4), S2: Proportional gain P (0-100), S3: Integral Time I (0-10000), S4: Derivative control D (0-100)

Explanation:

1.This command FPID can control the PID parameters of the AC motor drive directly, including Pr.10.00 PID set point selection, Pr.10.02 Proportional gain (P), Pr.10.03

Integral time (I) and Pr.10.04 Derivative control (D)

Program Example:

1.Assume that when M0=ON, S1 is set to 0 (PID function is disabled), S2=0, S3=1 (unit: 0.01 seconds) and S4=1 (unit: 0.01 seconds).

2.Assume that when M1=ON, S1 is set to 0 (PID function is disabled), S2=1 (unit: 0.01), S3=0 and S4=0.

3.Assume that when M2=ON, S1 is set to 1(frequency is inputted by digital keypad), S2=1 (unit: 0.01), S3=0 and S4=0.

4.D1027: frequency command controlled by PID.

D-62

Revision June 2008, 04EE, SW--PW V1.11/CTL V2.11