Delta Electronics VFD-E manual Error LED, Sp Led, LED on, Led Off

Models: VFD-E

1 363
Download 363 pages 22.75 Kb
Page 271
Image 271

Appendix B Accessories

ERROR LED

 

LED Status

State

 

Indication

 

OFF

No error

 

CME-COP01 is working condition

 

 

 

 

 

 

Single Flash

 

 

At least one of error counter of the

 

Warning limit reached

 

CANopen controller has reached or

 

(Red)

 

exceeded the warning level (too many

 

 

 

 

 

 

error frames)

 

 

 

 

 

 

 

 

 

 

Double Flash

Error control event

 

A guard event or heartbeat event has

 

(Red)

 

occurred

 

 

 

 

 

 

 

 

 

 

 

 

 

Red ON

Bus-off

 

The CANopen controller is bus-off

 

 

 

 

 

 

SP LED

 

 

 

 

LED Status

State

 

Indication

 

OFF

No Power

 

No power on CME-COP01 card

 

 

 

 

 

 

LED Blinking

CRC check error

 

Check your communication setting in

 

(Red)

 

VFD-E drives (19200,<8,N,2>,RTU)

 

 

 

 

 

 

 

1. Check the connection between

 

 

 

 

VFD-E drive and CME-COP01

 

Red ON

Connection failure/No

 

card is correct

 

connection

 

2. Re-wire the VFD-E connection and

 

 

 

 

 

 

 

ensure that the wire specification is

 

 

 

 

correct

 

LED Blinking

CME-COP01 returns error

 

Check the PLC program, ensure the

 

(Green)

code

 

index and sub-index is correct

 

Green ON

Normal

 

Communication is normal

 

LED Descriptions

 

 

 

 

State

 

Description

 

LED ON

Constantly on

 

 

 

 

 

 

 

 

LED OFF

Constantly off

 

 

 

 

 

 

LED blinking

Flash, on for 0.2s and off for 0.2s

 

 

 

 

 

 

LED single

On for 0.2s and off for 1s

 

 

 

flash

 

 

 

 

 

 

 

 

 

 

 

 

LED double

On for 0.2s off for 0.2s, on for 0.2s and off for 1s

 

flash

 

 

 

 

 

 

 

 

 

B-34

Revision June 2008, 04EE, SW--PW V1.11/CTL V2.11

Page 271
Image 271
Delta Electronics VFD-E manual Error LED, Sp Led, LED on, Led Off