Chapter 4 Parameters

The motor auto tune procedure will set this parameter. The user may also set this parameter

without using Pr.07.04.

07.06

Motor Rated Slip (Motor 0)

Unit: 0.01

 

 

 

 

 

Settings

0.00 to 20.00Hz

Factory Setting: 3.00

Refer to the rated rpm and the number of poles on the nameplate of the motor and use the following equation to calculate the rated slip.

Rated Slip (Hz) = Fbase (Pr.01.01 base frequency) – (rated rpm x motor pole 120)

07.07

Slip Compensation Limit

Unit: 1

 

Settings

0 to 250%

Factory Setting: 200

 

 

 

 

This parameter sets the upper limit of the compensation frequency (the percentage of Pr.07.06).

Example: when Pr.07.06=5Hz and Pr.07.07=150%, the upper limit of the compensation frequency is 7.5Hz. Therefore, for a 50Hz motor, the max. output is 57.5Hz.

07.08

Torque Compensation Time Constant

Unit: 0.01

 

Settings

0.01 ~10.00 sec

Factory Setting: 0.10

 

 

 

07.09

Slip Compensation Time Constant

Unit: 0.01

 

Settings

0.05 ~10.00 sec

Factory Setting: 0.20

 

 

 

 

Setting Pr.07.08 and Pr.07.09 changes the response time for the compensations.

Too long time constants give slow response; too short values can give unstable operation.

07.10

Accumulative Motor Operation Time (Min.)

Unit: 1

 

Settings

0~1439

Factory Setting: 0

 

 

 

07.11

Accumulative Motor Operation Time (Day)

Unit: 1

 

Settings

0 ~65535

Factory Setting: 0

 

 

 

Pr.07.10 and Pr.07.11 are used to record the motor operation time. They can be cleared by

setting to 0 and time is less than 1 minute is not recorded.

 

 

 

 

07.12

Motor PTC Overheat Protection

Unit: 1

 

 

 

 

Factory Setting: 0

 

Settings

0

Disable

 

 

 

1

Enable

 

 

 

 

07.14

Motor PTC Overheat Protection Level

Unit: 0.1

4-98

Revision June 2008, 04EE, SW--PW V1.11/CTL V2.11