Group 13: PG function Parameters for Extension Card

 

 

 

 

 

 

 

Parameter

Explanation

Settings

Factory

Customer

Setting

 

 

0: Disabled

 

 

13.00

PG Input

1: Single phase

0

 

2: Forward/Counterclockwise rotation

 

 

 

 

 

 

 

3: Reverse/Clockwise rotation

 

 

 

 

 

 

 

13.01

PG Pulse Range

1 to 20000

600

 

 

 

 

 

 

13.02

Motor Pole Number

2 to 10

4

 

(Motor 0)

 

 

 

 

 

 

 

 

 

 

13.03

Proportional Gain

0.0 to 10.0

1.0

 

(P)

 

 

 

 

 

 

 

 

 

 

13.04

Integral Gain (I)

0.00 to 100.00 sec

1.00

 

 

Speed Control

 

 

 

13.05

Output Frequency

0.00 to 100.00Hz

10.00

 

 

Limit

 

 

 

13.06

Speed Feedback

0 to 9999 (*2ms)

500

 

Display Filter

 

 

 

 

 

 

 

 

 

 

 

Detection Time for

0.0: disabled

 

 

13.07

Feedback Signal

1

 

0.1 to 10.0 sec

 

 

Fault

 

 

 

 

 

 

 

 

 

 

 

 

Treatment of the

0: Warn and RAMP to stop

 

 

 

 

 

 

13.08

Feedback Signal

1: Warn and COAST to stop

1

 

 

Fault

2: Warn and keep operation

 

 

 

 

 

 

 

 

 

 

 

13.09

Speed Feedback

0 to 9999 (*2ms)

16

 

Filter

 

 

 

 

 

 

 

 

 

 

13.10

Source of the High-

0: PG card

Read

 

 

 

speed Counter

1: PLC (NOT for VFD*E*C models)

Only

 

 

 

 

 

 

 

 

 

 

 

 